IBC construction types (Type I to V)

The International Building Code sorts buildings into five construction types, I through V, by how combustible the structure is and how long it must resist fire. Types I and II are noncombustible, Type III has noncombustible exterior walls, Type IV is heavy or mass timber, and Type V allows any material. Subtype A carries higher ratings than B.

Last reviewed October 2026

Helonic is an AI construction drawing analysis platform for teams researching construction types guide during drawing review. Below: the IBC 2021 Table 601 ratings for every type, what sets each type apart, and how sprinklers and frontage change allowable height and area.

What fire-resistance ratings does IBC Table 601 require for each construction type?

IBC 2021 Table 601 sets the hourly rating for each building element, from 3 hours for a Type I-A frame down to 0 for Type II-B, III-B, and V-B. Values are in hours.

IBC 2021 Table 601 fire-resistance ratings in hours by construction type
TypeCombustibilityPrimary structural frameExterior bearing wallsInterior bearing wallsFloorRoofTypical use
Type I-ANoncombustible33321½High-rise buildings, hospitals
Type I-BNoncombustible22221Mid-rise offices, schools
Type II-ANoncombustible11111Low-rise commercial
Type II-BNoncombustible00000Warehouses, big-box retail
Type III-ANoncombustible exterior walls, interior any permitted material12111Wood-frame apartments with rated exterior walls
Type III-BNoncombustible exterior walls, interior any permitted material02000Small commercial with masonry walls
Type IV-AMass timber with noncombustible protection33321½Tall mass timber
Type IV-BMass timber, limited exposed timber22221Mid-rise mass timber
Type IV-CMass timber, exposed timber permitted22221Low and mid-rise mass timber
Type IV-HTNoncombustible exterior walls, heavy timber interiorHT21 or HTHTHTHeavy timber, mill buildings
Type V-ACombustible (any permitted material)11111Protected wood-frame apartments
Type V-BCombustible (any permitted material)00000Unprotected wood frame, small commercial

Source: IBC 2021 Table 601. HT = heavy timber sized per IBC 2304.11. Table 601 footnotes change several values, for example letting the frame and bearing walls drop by 1 hour where they support only a roof, so read them before applying a number. Exterior nonbearing wall ratings come from Table 705.5 and depend on fire separation distance. Check the edition your jurisdiction adopted.

What is type of construction?

Type of construction classifies a building by the combustibility and fire resistance of its structural elements. It works together with the IBC occupancy classification: occupancy group plus construction type sets how tall and how large the building can be.

Type of construction affects:
  • Maximum allowable building height (stories and feet)
  • Maximum allowable building area
  • Allowable occupancies
  • Required ratings for walls, floors, and roofs, which show up as fire-rated wall assemblies on the drawings
  • Sprinkler and alarm requirements

What distinguishes each IBC construction type?

IBC construction types I through V are distinguished by whether the structure is noncombustible and how much fire resistance those elements must have.

Type I (noncombustible, fire-resistive)

Steel or concrete structure with the highest ratings in Table 601. Type I-A has no height limit, and Type I-B covers most mid-rise and many high-rise buildings.

Type II (noncombustible)

Steel or concrete structure with low or no ratings. Type II-A carries 1-hour protection; Type II-B is unprotected. Common for warehouses, retail, and low-rise offices.

Type III (noncombustible exterior walls)

Exterior walls are noncombustible, typically masonry or concrete, and the interior structure can be wood. IBC 602.3 also allows fire-retardant-treated wood framing in exterior walls rated 2 hours or less.

Type IV (heavy timber and mass timber)

Type IV-HT is traditional heavy timber, where large member sizes give the fire resistance. The 2021 IBC added Types IV-A, IV-B, and IV-C for mass timber such as CLT and glulam. For most sprinklered occupancies, Table 504.3 allows 270 feet for IV-A, 180 feet for IV-B, and 85 feet for IV-C.

Type V (any material)

Any material the code permits, including light wood framing. Type V-A requires 1-hour protection of the structure; Type V-B has no rating requirements.

How can height and area limits be increased by construction type?

Height and area limits can increase with sprinklers, frontage, and some mixed-occupancy calculations allowed by the IBC.

Sprinklers

An NFPA 13 system typically adds one story and 20 feet of height, and Table 506.2 sprinklered area factors run three to four times the nonsprinklered value.

Frontage

Open perimeter access for firefighting can increase area up to 75% (IBC 506.3)

Unlimited Area

Certain combinations of sprinklers, frontage, and low-hazard uses allow unlimited area (IBC 507)

IBC construction type FAQs

What is the difference between Type I-A and Type I-B construction?

Both are noncombustible, but Type I-A carries higher ratings in IBC 2021 Table 601: 3 hours for the primary structural frame and bearing walls against 2 hours for Type I-B. Type I-A has no height limit, while Type I-B is limited to 180 feet for most occupancies when sprinklered.

Can a wood-frame building be Type III construction?

Yes. Type III requires noncombustible exterior walls, and interior structural elements can be any material the code allows, including wood framing. IBC 602.3 also allows fire-retardant-treated wood framing in exterior walls rated 2 hours or less, which is why many wood-frame apartment buildings are Type III-A.

What are Type IV-A, IV-B, and IV-C construction?

They are the mass timber construction types added in the 2021 IBC. All three use mass timber such as cross-laminated timber for the structure. Type IV-A requires noncombustible protection over the mass timber, Type IV-B allows limited exposed timber, and Type IV-C allows exposed timber except in shafts and concealed spaces.

How do sprinklers affect allowable building height and area?

An NFPA 13 system typically adds one story and 20 feet of height under IBC Tables 504.3 and 504.4, and the sprinklered area factors in Table 506.2 run three to four times the nonsprinklered value. For example, a Type V-A building limited to 50 feet without sprinklers can reach 70 feet for most occupancies when fully sprinklered.

Sources & References

  • International Building Code (IBC) 2021, Chapter 6: Types of Construction
  • IBC 2021, Table 601: Fire-Resistance Rating Requirements for Building Elements (Hours)
  • IBC 2021, Section 602.4: Type IV construction (IV-A, IV-B, IV-C, IV-HT)
  • IBC 2021, Table 504.3: Allowable Building Height in Feet Above Grade Plane
  • IBC 2021, Table 504.4: Allowable Number of Stories Above Grade Plane
  • IBC 2021, Table 506.2: Allowable Area Factor

Note: Local jurisdictions may have amendments to the IBC. Always verify requirements with your Authority Having Jurisdiction (AHJ).